节点文献

地下岛式地铁站台火灾时全封闭屏蔽门开启模式研究

Study on switch modes of fully enclosed platform screen doors during fire in underground railway island-type platform

  • 推荐 CAJ下载
  • PDF下载
  • 不支持迅雷等下载工具,请取消加速工具后下载。

【作者】 李建史聪灵陈长坤胥旋

【Author】 LI Jian;SHI Congling;CHEN Changkun;XU Xuan;Beijing Key Laboratory of Metro Fire and Passenger Transportation Safety,China Academy of Safety Science and Technology;Institute of Disaster Prevention Science and Safety Technology,Central South University;

【机构】 中国安全生产科学研究院地铁火灾与客流疏运安全北京市重点实验室中南大学防灾科学与安全技术研究所

【摘要】 为研究4种屏蔽门开启模式下地下岛式站台火灾时排烟效果,本文采用大涡模拟进行计算,研究的开启模式包括开启两侧共4个端门、开启两侧首尾活动门及中间活动门和开启一侧所有活动门、开启两侧所有活动门。着重研究站台危险高度和楼扶梯口处烟气温度、CO浓度、可见度以及顶棚烟气温度。研究发现火灾发展阶段开启两侧屏蔽门首尾及中间活动门的排烟效果最好,火灾稳定阶段开启一侧所有活动门排烟效率较高,开启两侧所有活动门虽然能够加大烟气流出开口,但是排烟效果最差。

【Abstract】 The large eddy simulation was applied for calculation to investigate the smoke exhaust effect during fire in underground island- type platform under four different switch modes of platform screen doors,which include opening four end doors at both sides,opening the head and tail trapdoors at both sides and middle trapdoors,opening all the trapdoors at one side,and opening all the trapdoors at both sides. The smoke temperature,CO concentration and visibility at dangerous height of platform and stair head were studied with emphasis,as well as the smoke temperature at ceiling. The results showed that in fire development stage,the smoke exhaust effect was the best when opening the head and tail trapdoors at both sides and middle trapdoors,while in fire stable stage,the smoke exhaust efficiency was the highest when opening all the trapdoors at one side. When opening all the trapdoors at both sides,although the smoke flow openings can be enlarged,the smoke exhaust effect was the worst.

【基金】 国家自然科学基金项目(51622403、51274176、51576212);十三五国家重点研发计划项目(2016YFC0802505);中国安全生产科学研究院基本科研业务费专项项目(2016JBKY04、2016JBKY19、2016JBKY20)
  • 【文献出处】 中国安全生产科学技术 ,Journal of Safety Science and Technology , 编辑部邮箱 ,2016年11期
  • 【分类号】U231.96
  • 【被引频次】15
  • 【下载频次】251
节点文献中: