节点文献

一起热电厂三相电流不平衡现象调查分析

Investigation and Analysis of a Three Phase Current Unbalance Phenomenon in Thermal Power Plant

  • 推荐 CAJ下载
  • PDF下载
  • 不支持迅雷等下载工具,请取消加速工具后下载。

【作者】 金百荣李电

【Author】 JIN Bai-rong,LI Dian (Shaoxing Power Supply Bureau,Shaoxing 312000,China)

【机构】 绍兴电力局

【摘要】 介绍了一起热电厂因线路割接后频繁出现三相电流不平衡现象,并根据电能质量在线监测系统历史数据,确认异常原因为上级电网电气化铁道负荷产生的负序电流引起,显示出电铁负荷造成的负序电流污染影响范围十分深远,发电机对系统负序电压十分敏感。

【Abstract】 A three phase current unbalance phenomenon after replacement of power line in a thermal power plant is introduced.Based on the historical data of on-line power quality monitoring system,it is confirmed that the abnormal phenomenon is caused by the negative sequence current produced by electric railway load from upper power grid;it is shown that the pollution influence of negative sequence current produced by electric railway load is very wide,and the generator is very sensitive to negative sequence voltage.

  • 【文献出处】 电力电容器与无功补偿 ,Power Capacitor & Reactive Power Compensation , 编辑部邮箱 ,2012年01期
  • 【分类号】TM727.3
  • 【被引频次】1