【摘要】 当发电机外部短路时,由于电流互感器的暂态误差,使比率制动式发电机纵差保护的制动电流减小,如不考虑它的影响,有可能造成外部短路时保护误动作。为此,讨论在整定计算中计及制动电流减小的影响时,适当提高最大制动系数的方法。

【Abstract】 In case of generator external short circuit, due to the transient error on current transformers, the braking current on percentage braking type longitudinal differential protection of generator might be lowered. If this effect is ignored, it is possible to cause a mal-operation on protection during external short circuit. For this reason, the paper discusses the method of calculation concerning the effect of braking current decrease by adequately increasing the maximum braking coefficient.

  • 【文献出处】 中国电力 ,ELECTRIC POWER , 编辑部邮箱 ,2000年03期