节点文献

北仑发电厂600MW锅炉高温再热器超温问题原因分析及改造

Causes Analysis of Overtemperature Problem of 600 MW Boiler’s High Temperature Reheater in Beilun Power Plant

  • 推荐 CAJ下载
  • PDF下载
  • 不支持迅雷等下载工具,请取消加速工具后下载。

【摘要】 分析了北仑发电厂600 M W 锅炉再热器局部超温及旁路改造未能达到预期效果的原因;详细介绍了采用在低温管屏中加节流圈为主的改造方案和计算过程。改造后最高温度屏的出口壁温下降了10 ~15 ℃,提高了机组的运行可靠性,节流圈引起的再热器阻力增加只有11 k Pa ,改造后电厂的直接经济效益为每年170 万元。

【Abstract】 The causes for local overtemperature of high temperature reheater of 600 MW boiler in Beilun Power Plant and that bypass retrofit could not realize the expected effect are analyzed;the retrofitting scheme by fitting throttle rings in low temperature reheater platen and calculation process are described in detail.After retrofit,the wall temperature at the outlet of the highest temperature platen decreased by 10~15 ℃ with unit’s operation reliability improved.The increase in reheater resistance as a result of throttle rings only amounted to 11 kPa,the direct economic benefit of power plant reached 1 7 million yuan.

  • 【文献出处】 中国电力 ,ELECTRIC POWER , 编辑部邮箱 ,1999年09期
  • 【分类号】TM621.3
  • 【被引频次】9
  • 【下载频次】211
节点文献中: