节点文献
母联(分段)开关保护的整定与运行策略
Fixing and Running Policy of Bus Coupling(Subsection) Breaker Protection
【摘要】 介绍了在母联开关或分段开关设置一套独立保护装置的必要性,阐述了该独立保护装置的常见配置方案,即配置了一套完整的线路保护或配置了由1段短充电保护和2段长充电保护构成的长充电保护,分析了后加速保护与短充电保护和电流保护与长充电保护原理,提出了母联(分段)开关保护的运行策略和整定策略,这些运行策略和整定策略通过实践证明是有效的。
【Abstract】 This paper introduces the necessity to set an unattached relay protection equipment for bus coupling or subsection breaker and expatiates the general project of this unattached relay protection equipment,viz.configuring a set of integrated bus-protection or a set of charging-protection made up of a section of short time charging-protection and two section of long time charging-protection.The paper also analyses the principle of after-speedup protection adding short time charging-protection and current protection adding long time charging-protection.According to above analysis,the fixing and running policy is presented,which is proven to be effective in practice.
【Key words】 bus coupling breaker; section breaker; relay protection equipment; fixing and running policy;
- 【文献出处】 江苏电机工程 ,Jiangsu Electrical Engineering , 编辑部邮箱 ,2007年04期
- 【分类号】TM774
- 【下载频次】152