两级A/O工艺处理生活污水脱氮除磷试验
Nitrogen and phosphorus removal from domestic sewage by two-stage A/O process
【摘要】 针对传统A2/O工艺存在的泥龄矛盾,将脱氮和除磷分置于前后2套不同的A/O系统中,第一级A/O采用活性污泥法除磷;第二级A/O采用生物膜法脱氮。以生活污水为处理对象进行试验研究。结果表明,在泥龄为6 d、水温为22~28℃,进水NH3-N、TP、COD的质量浓度分别为40~70、2.0~6.0、150~320 mg/L条件下,出水NH3-N、TP、COD的平均质量浓度分别为5.9、1.0、40 mg/L,均达到了城镇污水处理厂污染物排放标准(GB18918-2002)中的一级排放标准,其去除率分别为82.5%、69.7%、83.1%。
【Abstract】 To solve the SRT contradiction existed in the traditional A2/O process,technologies for nitrogen removal and phosphorus removal were used separately in two different A/O systems,Phosphorus was removed in the first A/O process with activated sludge technology,and then,nitrogen was removed in the second A/O process with biological film technology.A study was carried out with domestic sewage as treatment object,the results showed that,under the condition that,the SRT was 6 d,the temperature was 22-28 ℃,the mass concentration of NH3-N,TP,COD in influent water were 40-70,2.0-6.0,150-320 mg/L respectively,the mass concentration of NH3-N,TP,COD in effluent water were 5.9,1.0,40 mg/L in average respectively,which met the specification for grade 1 in Discharge standard of pollutants for municipal wastewater treatment plant(GB 18918-2002),the removal rate of the above three pollutants were 82.5%,69.7%,83.1% respectively.
【Key words】 two-stage A/O process; A2/O process; nitrogen and phosphorus removal by biological process;
- 【文献出处】 工业用水与废水 ,Industrial Water & Wastewater , 编辑部邮箱 ,2007年01期
- 【分类号】X799.3
- 【被引频次】2
- 【下载频次】624