节点文献

变压器矿物油中糠醛的稳定性研究

Stability of Furfural Dissolved in Transformer Mineral Oil

  • 推荐 CAJ下载
  • PDF下载
  • 不支持迅雷等下载工具,请取消加速工具后下载。

【作者】 向彬廖瑞金杨丽君冯运李剑

【Author】 XIANG Bin1,LIAO Rui-jin1,YANG Li-jun1,FENG Yun1,2,LI Jian1(1.The Key Laboratory of High Voltage and Electrical New Technology of Ministry of Education,Chongqing University,Chongqing 400044,China;2.Sichuan Electric Power Test of Research Institute,Chengdu 610072,China)

【机构】 重庆大学高电压与电工新技术教育部重点实验室重庆大学高电压与电工新技术教育部重点实验室 重庆400044重庆400044四川电力试验研究院成都610072

【摘要】 为了掌握糠醛在变压器运行环境下的化学稳定特性,提高利用糠醛判断油浸式变压器绝缘老化程度的可靠性,充分参考变压器实际运行环境,设计了矿物油中存在金属铜和硅钢片的情况下,3个不同初始质量浓度的糠醛分别在80°C和130°C下的稳定性实验。通过定期取样测量表明,在2个实验温度下,油中糠醛质量浓度均随时间呈线性关系下降。相同糠醛初始质量浓度下,温度越高,糠醛消耗速度越快。相同温度下,油中糠醛的初始质量浓度越高,其消耗速度越快。可见,矿物油中糠醛的消耗速度与变压器运行温度和油中糠醛初始质量浓度有关,实际工程中利用糠醛来判断变压器纸绝缘老化程度时,应参考变压器的运行温度及油中糠醛的历史记录情况。

【Abstract】 In order to investigate the chemical stability characteristic of furfural under the transformer operating conditions and to improve reliability of aging conditions for transformer insulation paper estimated with furfural indicator,according to the filed operating conditions of transformer,the furfural stability experiment in laboratory conditions similar to practical conditions of field transformer is designed.Three different initial concentrations of furfural,dissolved in transformer mineral oil with the copper and silicon steel,at 80 °C and 130 °C are used.By the periodic sampling and measuring,the results indicate that with effect of temperature and metal,the mass of furfural in oil decreases and the good linear relationship between concentration of furfural and time is found at the two temperatures.Under the same initial concentration of furfural,the higher the temperature is,the faster the loss rate of furfural becomes.In addition,it is also found that the higher the initial concentration of furfural at the same temperature is,the faster the lost rate of furfural becomes.Therefore,the lost rate of furfural is related to the operating temperature of transformer and the initial concentrations of furfural.Then,when furfural is used to estimate transformer insulation conditions in practice,both the operating temperature and the historical concentrations of furfural should be considered at the same time.In order to know about the chemical stable characteristic of furfural under the transformer operating conditions and improve reliability of aging conditions for transformer insulation paper estimated with furfural indicator.In the paper,according to the filed operating conditions of transformer,the furfural stability experiment in laboratory conditions which is similar to practical conditions of field transformer is designed.Three different initial concentrations of furfural,dissolved in transformer mineral oil with the copper and silicon steel,at 80°C and 130°C are carried out.By the periodic sampling and measuring,the results indicate that with effect of temperature and metal,a mass of furfural in oil decrease and the good linear relationship between concentration of furfural and time is still found at the two temperatures.Under the same initial concentration of furfural,the temperature is higher,the loss rate of furfural becomes faster.In addition,it is also found that the initial concentration of furfural at the same temperature is higher,the lost rate of furfural becomes faster.Therefore,the lost rate of furfural is relation to the operating temperature of transformer and the initial concentrations of furfural.Then,when furfural is used to estimate transformer insulation conditions in practice,both the operating temperature and the bhistorical concentrations of furfural should be considered at the same time.Furfural is the special decomposition product which is generated by the degradation of cellulose in insulation paper but not by insulation oil.As an important indicator,furfural has been widely used to estimate aging conditions of insulation paper in oil immersed power transformers.In order to know about the chemical stable characteristic of furfural under the transformer operating conditions and improve reliability of aging conditions for transformer insulation paper estimated by furfural.In the paper,according to the filed operating conditions of transformers,the furfural stability experiment in laboratory conditions which is similar to practical conditions of field transformer is designed.Three different initial concentrate furfurals,dissolved in transformer mineral oil,with the copper and silicon steel at 80°C and 130°C are carried out.By the periodic sampling and measuring,the results indicate that with effect of temperature and metal,a mass of furfural in oil decrease and the good linear relationship between concentration of furfural and time is still found at the two temperatures.The concentration of furfural in oil slow down with the proportion to about 20% initial concentration value at 80°C,but almost work out at 130°C in about 800 hours.In addition,it is also found that the initial concentration of furfural at the same temperature is higher,the lost rate of furfural becomes faster.Therefore,the lost rate of furfural in oil is relation to the operating temperature of transformer and the initial concentration of furfural.The temperature is higher,the lost rate of furfural becomes faster,and the initial concentration of furfural dissolved in oil is larger,the lost rate of furfural also become faster.

【关键词】 变压器老化矿物油糠醛稳定性温度金属
【Key words】 transformeragingmineral oilfurfuralstabilitytemperaturemetal
【基金】 国家杰出青年基金(50425722);重庆市自然科学基金(11699)。~~
  • 【文献出处】 高电压技术 ,High Voltage Engineering , 编辑部邮箱 ,2007年08期
  • 【分类号】TM404
  • 【被引频次】40
  • 【下载频次】269
节点文献中: 

本文链接的文献网络图示:

本文的引文网络