隔离病房和缓冲室的换气次数与冷负荷匹配情况对温差和隔离系数的影响

Influence of different combinations of air changes and cooling load in isolation wards and buffer rooms on temperature difference and isolation coefficient

  • 推荐 CAJ下载
  • PDF下载
  • 不支持迅雷等下载工具,请取消加速工具后下载。

【作者】 冯昕; 许钟麟; 张益昭;

【Author】 By Feng Xin★,Xu Zhonglin and Zhang Yizhao★Institute of Air conditioning, China Academy of Building Research, Beijing, China

【机构】 中国建筑科学研究院空气调节研究所; 中国建筑科学研究院空气调节研究所;

【摘要】 从理论上分析了考虑温差影响下,隔离病房和缓冲室的换气次数与房间冷负荷的匹配情况对两室一缓工况下隔离效果的影响。通过定量分析计算,指出隔离病房和缓冲室间的温差和隔离系数主要由两室的换气次数与房间冷负荷的匹配情况确定,而病房匹配情况的影响要比缓冲室大得多。

【Abstract】 Based on the previous research,theoretically analyses the influence of combinations of air changes and cooling load in an isolation ward and the adjacent buffer room on isolation effects when the temperature difference is considered. According to a quantitative analysis,concludes that the matching relationship between air changes and cooling load is a major factor in determining the actual temperature difference and isolation coefficient,and that the parameters in isolation ward would play a dominant role.