Test validation of parameters in standard for middle and small glass fiber reinforced plastic cooling tower
【摘要】 通过试验,验证了GB7190.1-1997玻璃纤维增强塑料冷却塔第1部分:中小型玻璃纤维增强塑料冷却塔标准中湿球温度、进塔水温及相对湿度3个参数对冷却塔冷却效率的影响,试验数据表明,湿球温度、相对湿度及进塔水温对冷却塔的测试结果基本上没有影响;对冷却塔的进水温度的要求还可以适当放宽到31.5℃。
【Abstract】 A test was carried out to validate the content of GB7190.1-1997 glass fiber reinforced plastic cooling tower,Part one,i.e.the effect of the three parameters: wet bulb temperature,supply water temperature,and relative humidity in standard for small glass fiber reinforced plastic cooling tower on the cooling efficiency of cooling tower.The testing data showed that,wet bulb temperature,relative humidity,and influent water temperature had little influence on the testing result,the range required for influent water temperature of cooling tower could be broaden to 31.5℃.
【Key words】 cooling tower; cooling efficiency; wet bulb temperature; influent water temperature; relative humidity;