节点文献
220kV电容式电压互感器的隐患事故分析
Analysis of 220kV Capacitor Voltage Transformer’s Hidden Fault
【摘要】 通过现场测试,发现电容式电压互感器的电容量误差在国家标准之内,但电容量异常增加,且三相线电压明显不平衡,经进一步试验分析,判定电容器内部串联电容已部分击穿,提出了电容式压变运行及测试相应注意事项。
【Abstract】 Based on the practical tests,It is found that the CVT’s capacitance increases abnormally,and the three phase voltages are obviously imbalanced,although the error of CVT′s capacitance is within the requirement specified by the national standard.Through further examination,it can be concluded that the inner in-series capacitors have been partly broken down.The attentions on CVT′s operation and testing are proposed.
- 【文献出处】 电力电容器 ,Power Capacitor , 编辑部邮箱 ,2006年03期
- 【分类号】TM451.2
- 【下载频次】76