节点文献

VFT PHASE VOLTAGE MEASUREMENT IN THREE-PHASE ENCLOSED GIS

  • 推荐 CAJ下载
  • PDF下载
  • 不支持迅雷等下载工具,请取消加速工具后下载。

【作者】 邹建华岳子丁李洋

【Author】 Zou Jianhua, Yue Ziding, Li YangSystems Engineering Institute, Xi’an Jiaotong University, Xi’an 710049, China.

【机构】 Systems Engineering InstituteXi’an Jiaotong UniversityXi’an Jiaotong University Xi’an 710049ChinaXi’an 710049China

【Abstract】 The measuring of VFT phase voltage in three-phase enclosed GIS is more complex and difficult than in single-phase ones. There are 3 capacitive sensors in the measuring system, the outputs of which are with a linear relation to the three phase voltages. This linear relation is presented with a factorial matrix. Because each capacitive sensor is coupled with the electric field of three phases (A, B, and C), the electric coupling coefficients are introduced. In order to determine the matrix of electric coupling coefficients, the numerical calculation method can be used. From the discussion on two types of three-phase enclosed GIS bus, i.e. standard arrangement and biased arrangement, the dominant electric coupling coefficients are named, which can be simply and approximately calculated by an analytic expression. Finally, as an example, the waveforms of VFT phase voltage generated on a three-phase enclosed GIS bus model are displayed. When a capacitive sensor is located at the ’shortest point’ of phase A (or B, or C), the VFT phase voltage V A (or V B, or V C) can almost be measured by that capacitive sensor alone.

  • 【文献出处】 Academic Journal of Xi’an Jiaotong University ,西安交通大学学报(英文版) , 编辑部邮箱 ,2002年02期
  • 【分类号】TM933
  • 【被引频次】1
  • 【下载频次】32
节点文献中: 

本文链接的文献网络图示:

本文的引文网络