节点文献
风机盘管水系统电磁阀总开启率的变化范围及其影响
Possibility analysis of the fan-coil unit water system
【摘要】 过概率计算 ,指出在某确定的中、高负荷率下 ,末端通断控制的风机盘管水系统的阻力特性和总水量将波动不大 ,此时水系统可取消制冷机的旁通管 ,并且直接应用一次泵变频。
【Abstract】 Based on the analysis reaches the conclusion that the resistant coefficient and total water flow rate will fluctuate to a very limited extent at a medium or high load level in the chilled water system with on-off controlled fan coil units therefore the bypass pipe on the chiller becomes nonessential and the system can be simply one with variable speed primary pumps.
【关键词】 空调;
冷水系统;
节能;
变速泵;
【Key words】 air conditioning; chilled water system; energy efficiency; variable speed pump;
【Key words】 air conditioning; chilled water system; energy efficiency; variable speed pump;
- 【文献出处】 暖通空调 ,Hv & Ac , 编辑部邮箱 ,2002年06期
- 【分类号】TU831.6
- 【被引频次】19