电流保护两种接线形式的灵敏度分析

Sensitivity analysis for electricity defensive two wiring connections

  • 推荐 CAJ下载
  • PDF下载
  • 不支持迅雷等下载工具,请取消加速工具后下载。

【作者】 朱雪凌张建成

【Author】 ZHU Xue ling 1 , ZHANG Jian cheng 2 (1.North China Institute of Water Conservancy and Hydroelectric Power, Zhengzhou 450045, China; 2. Gongyi First Power Plant, Zhengzhou 451200, China)

【机构】 华北水利水电学院动力系巩义市第一发电厂 河南郑州450045河南郑州451200

【摘要】 就三相三继电器完全星形接线与两相两继电器的不完全星形接线在Y ,d11接线变压器后发生两相短路时的灵敏度进行了分析与探讨 .若采用完全星形接线 ,在任何两相发生相间短路时 ,保护装置的灵敏度均较高 ;而采用不完全星形接线 ,在某两相发生相间短路时 ,保护装置的灵敏度将减小一半 ,但可采取在其公共线上接入第三个电流断电器的方法提高其灵敏度 .

【Abstract】 The sensitivity is analysed and discussed during two phase short circuit, after Y,d11 transformer,of relays on three phase complete star connection and two phase incomplete star connection.For complete star connection, the sensitivity of protection device is high when any two phase short circuit happens, while for incomplete star connection, the sensityvity is deducted by half. However, a third circuit relay can be used on common lines in order to improve the sensitivity.

  • 【文献出处】 华北水利水电学院学报 ,Journal of North China Institute of Water Conservancy and Hydroelectric Power , 编辑部邮箱 ,2002年01期