节点文献

GIS隔离开关操作对二次设备的影响

The Effects of Operations of the Disconnector Switch on the Secondary Circuits in Gas Insulated Substations

  • 推荐 CAJ下载
  • PDF下载
  • 不支持迅雷等下载工具,请取消加速工具后下载。

【摘要】 简述了 GIS内的电磁兼容问题及隔离开关操作产生 VFTO和 TGPR的机理、一次设备干扰二次设备的几种途径。在此基础上总结了现有的各种 VFTO和 TGPR以及二次电缆内干扰电压计算方法 ,并指出其不足 ,提出了一些改进的思路

【Abstract】 In this paper, the Electromagnetic Compatibility Problem the mechanism of the Very Fast Transient Overvoltage(VFTO) and the Transient Ground Potential Rise(TGPR) produced by Disconnentor Switch Operations in Gas Insulated Substation(GIS) are discussed in brief, and the several ways of primary circuits disturbing secondary circuits are summarized. Various methods for the computing of VFTO and TGPR as well as the disturbing voltage in secondary cables are sum up, the shortage of those methods are discussed, and amelioration idea is proposed.

【基金】 国家自然科学基金资助。 No.5 0 0 770 0 6
  • 【文献出处】 高电压技术 ,High Voltage Engineering , 编辑部邮箱 ,2002年02期
  • 【分类号】TM56
  • 【被引频次】108
  • 【下载频次】696
节点文献中: 

本文链接的文献网络图示:

本文的引文网络