湖北宝塔河变电站遥控误动事故分析

Analysis of Remote Control Accident in Baotahe Substation

  • 推荐 CAJ下载
  • PDF下载
  • 不支持迅雷等下载工具,请取消加速工具后下载。

【作者】 万磊漆啸海别钦

【Author】 WAN Lei 1,QI Xiao hai 2,BIE Qin 2 (1. Huazhong University of Science and Technology,Wuhan 430074,China; 2. Jingzhou Electric Power Dispatching and Telecommunication Bureau,Jingzhou 434002,China)

【机构】 华中科技大学电力系荆州电力调度通信局荆州电力调度通信局 湖北武汉430074湖北荆州434002湖北荆州434002

【摘要】 介绍了湖北省宝塔河变电站RTU遥控误动事故的经过 ,对发生事故的原因进行了分析 ,提出在无人值守变电站实现遥控功能时 ,RTU应采用遥控板外的校核方式 ,遥控电源与遥信电源分离 ,通道采用防雷放电器等技术措施。

【Abstract】 A remote control accident in Baotahe substation of Hubei province is introduced.After a thorough accident analysis, it is suggested that when remote control function is implemented in unmanned substation, following measures should be taken.The signal for control feed back check should not come from the same control card, the power for remote control and that for telemetering should be separated,the discharger against lightening should be adopted for communication channels,etc.