节点文献
大型发变组微机保护双重化配置探讨
DISCUSSION OF THE LARGE GENERATOR-TRANSFORMER UNIT REDUNDANT SETSOF PROTECTION SCHEME
【摘要】 提出了大型发变组微机保护进行双重化配置的新方案 ;介绍了采用 RCS— 985装置实现的大型发变组保护方案 ,即双套主保护、双套后备保护、双套异常运行保护配置 ,阐明了双主双后配置方案回路简单、运行维护方便的优点 ;对电流互感器和电压互感器的配置提出了看法 ,并针对实现双主双后需要解决的问题进行了探讨
【Abstract】 A new schem e of the large generator- transformer unitredundantsets of protection is proposed.The large generator transformer unitprotection scheme achieved in the protection equipment RCS- 985 is introduced in detail,which uses redundant sets of m ain protection,back- up protection schem e and abnormal protection of generator.Moreover,the advantages of simple circuit and convenience in operation of redundant sets of both the main and back- up protection schem es are illustrated. Especially,the configuration schem e of TA and TV is proposed and som e problem s of redundant sets of m ain and back- up protection schem e need to be solved are discussed.
【Key words】 relay protection; generator- transform er unit; reduntant sets of protection;
- 【文献出处】 电力系统自动化 ,Automation of Electric Power Systems , 编辑部邮箱 ,2002年10期
- 【分类号】TM773
- 【被引频次】54
- 【下载频次】261