节点文献
高压电缆护层故障测距新方法
An Accurate Cable Sheath Fault Distance Measurement Method
【摘要】 35KV以上高压单芯电缆护层绝缘破坏是一种比较常见的故障现象,目前的护层故障测距方法精度受导引线及接触电阻影响比较大.本文提出了测量电缆护层端头与故障点之间电阻的故障精确测距方法,介绍了新的测距方法实际使用中的几个问题,该方法具有测量精度高,简单、实用的优点.
【Abstract】 Sheath insulation damage is a very common fault type of single phase HV power cable. Accuracy of the existing sheath fault distance measurement methods is subject to test lead and contact resistance influence, and therefore is not satisfactory for practical fault location application. A new distance measurement method of cable sheath fault is introduced in this paper. It measures resistance of cable sheath between terminal and fault point. The proposed method is free from influence of test lead and contact resistance, simple and practically applicable.
- 【文献出处】 山东工程学院学报 ,Journal of Shandong Institute of Technology , 编辑部邮箱 ,1999年03期
- 【分类号】TM764
- 【下载频次】100