热管蒸气压缩复合式基站机房空调的设计与实验研究

DESIGN AND EXPERIMENTAL STUDY ON HEAT PIPE AND VAPOR COMPRESSION AIR CONDITIONER APPLIED IN BASE STATION

  • 推荐 CAJ下载
  • PDF下载
  • 不支持迅雷等下载工具,请取消加速工具后下载。

【作者】 吴银龙张华王子龙郭潇杨颜慧磊姜敬德

【Author】 Wu Yinlong;Zhang hua;Wang Zilong;Guo Xiaoyang;Institute of Refrigeration Technology,Shanghai University of Science and Technology;

【机构】 上海理工大学制冷技术研究所上海出入境检验检疫局机电产品检测技术中心

【摘要】 针对基站机房等内热源封闭的高热流密度空间换热存在的问题设计并搭建了一套重力型热管蒸气压缩复合式基站机房空调实验设备,介绍了系统的原理和特点,并对其实验研究。与传统基站机房空调相比,采用环保的R410A工质,系统可以在蒸气压缩制冷循环、热管循环和复合系统循环三种工作模式下自由切换,使系统在节能的模式下运行并提高系统的效率。根据实验结果,在室外环境为15℃时,复合系统在35度进风的时候制冷量可以达到18.5kw,能效比达到4.4,25度进风的时候也可以达到14.6kw,能效比达到3.5,系统不仅具有良好的可靠性、节能率在20%~55%之间具有可观的经济效益和市场推广价值。

【Abstract】 Designed and built a heat pipe and vapor compression air conditioner experimental equipment for the base stations and spaces which has heat transfer problems such as internal heat source enclosed and high heat flux,Introduced the principles and characteristics of the system,and its experimental study.Compared with the traditional base station air conditioning,the system use environmentally friendly refrigerant R410 A,the system can freely switch three operating modes:vapor compression refrigeration cycle,the heat pipe refrigeration cycle and complex system circulating,so the base station can run in energy-saving mode and improve efficiency.According to the experimental results,the outdoor environment is about 15℃,the composite system’ s refrigerating capacity can reach to 18.5 kw and the EER reach to 4.4when the inlet wind at 35℃,even the inlet wind at 25℃ the refrigerating capacity can also reach to 14.6 kw and the EER reach to3.5.The system not only has a good reliability,but also the energy-saving rate is between 20%~ 55%with considerable economic benefit and promotion value.

【关键词】 基站热管复合系统节能
【Key words】 Base stationHeat pipeComposite systemEnergy-saving
  • 【会议录名称】 2013中国制冷学会学术年会论文集
  • 【会议名称】勇于创新,服务发展——2013中国制冷学会学术年会
  • 【会议时间】2013-11-05
  • 【会议地点】中国湖北武汉
  • 【分类号】TB657.2
  • 【主办单位】中国制冷学会