谐波电流对换流变压器绕组损耗及温度分布特性的影响

The Influence of Harmonic Current on The Loss and Temperature Distribution Characteristics of a Converter Transformer Winding

  • 推荐 CAJ下载
  • PDF下载
  • 不支持迅雷等下载工具,请取消加速工具后下载。

【作者】 谭又博余小玲臧英王昊天李军浩

【Author】 Tan Youbo;Yu Xiaoling;Zang Ying;Wang Haotian;Li Junhao;School of Energy and Power Engineering Xi’an Jiaotong University;School of Chemical Engineering and Technology Xi’an Jiaotong University;Shandong Electric Power Equipment Co.Ltd;State Key Laboratory of Electrical Insulation and Power Equipment Xi’an Jiaotong University;

【通讯作者】 余小玲;

【机构】 西安交通大学能源与动力工程学院西安交通大学化学工程与技术学院山东电力设备有限公司西安交通大学电力设备电气绝缘国家重点实验室

【摘要】 针对谐波电流引起的换流变压器绕组局部过热、绝缘老化加速的问题,该文对现有绕组温度计算模型进行了改进,并采用电磁-热-流多物理场耦合的方法定量分析了谐波电流对绕组损耗和温度分布特性的影响规律。结果表明,采用该文提出的计算模型,绕组热点和平均温度与实测结果的误差分别为0.4%和2.9%,辐向油道内油流质量流量和线饼温度的分布规律与参考文献十分吻合。基波工况下,受涡流效应的影响,绕组端部附近2~3个线饼以及辐向内侧线饼单元的损耗明显较大。相比于基波工况,谐波电流不仅使各线饼的损耗增大,同时加剧了端部和辐向内侧线饼单元的涡流效应,使端部和辐向内侧线饼单元损耗显著增大,导致绕组温度沿辐向分布不均匀,热点集中在绕组辐向内侧,热点和平均温度分别升高了8.6℃和3.5℃。

【Abstract】 Since the harmonic current aggravated the local overheating and insulation aging of converter transformer windings, studying the influence of harmonic current on the loss and temperature distribution characteristics of windings attributed to improve the stability of transformer operation and prolong its service life.Accurate thermal modeling was critical for this study. However, there were different degrees of simplifications in the existing numerical calculation models of winding temperature. Moreover, most of current research focused on the influence of harmonic current on the loss and hot-spot temperature values, whereas there was a lack of quantitative analysis on the influence of harmonic current on the loss and temperature distribution characteristics of windings. To address these issues, this study improved winding temperature numerical calculation model, and based on this improved model, the influence of harmonic current on the loss and temperature distribution characteristics of windings was investigated.Firstly, a novel simplification method of disc was developed and an electromagnetic-thermo-flow coupling numerical model of a full-scale valve-side winding of a converter transformer practically applied in engineering was established, in which the key factors affecting the calculation accuracy of the winding temperature were comprehensively considered. The model was validated by both measured and literature results. Secondly, the losses and temperature of the winding under the fundamental wave and rated conditions were calculated,respectively. Finally, the influence of harmonic current on the loss and temperature distribution characteristics of the winding was quantitatively analyzed.The results showed that compared with the non-simplified model, the axial heat transfer rate of the simplified model established by the simplification method of disc proposed in this study was almost the same, and the deviation of the radial heat transfer rate was within 2%. Moreover, compared with the fundamental wave condition, under the rated condition, along the axial direction, the losses of the first to fourth disc in winding top increased by 64.86%, 51.29%, 43.06% and 37.45%, respectively, and the losses of the first to fourth disc in winding bottom increased by 65.71%, 53.55%, 45.49% and 40.36%, respectively. And along the radial direction, the total losses of each disc unit column increased by 41.69%, 32.61%, 24.83%, 18.87% and 15.40% from the innermost to the outermost column. Besides, under the fundamental wave condition, the winding hot-spot and mean temperatures were 81.7℃ and 74.3℃, respectively. The difference of winding temperature distribution along the radial direction was not obvious. By contrast, under the rated condition, the winding hot-spot and mean temperatures were 90.3℃ and 77.8℃, respectively. The winding temperature was unevenly distributed along the radial direction, and the hot spot was concentrated on the winding inside. The following conclusions were drawn:(1) The simplification method of disc proposed in this study was accurate for calculating the heat transfer of the disc. Compared with the traditional simplification method, i.e. electrothermal analogy, adopting the simplification method proposed in this study, not only the huge workload of establishing thermal resistance network was avoided and the computational hardness was lowered, but also this method was applicable to the special-shaped disc structure.(2) The uncertainty caused by partial simplification of existing numerical calculation models was reduced after adopting the multi-physics coupling model established in this work.(3) Compared with the fundamental wave condition, the harmonic current intensified the eddy current effect of the end and radial inside disc unit, which increased the losses of the end and radial inside disc unit.(4) Compared with the fundamental wave condition, the harmonic current made winding temperature unevenly distributed along the radial direction, and the hot spot was concentrated on the winding inside. The hot spot and mean temperatures were increased by 8.6℃ and 3.5℃, respectively.

【基金】 西安交通大学电力设备电气绝缘国家重点实验室(EIPE20206);国家电网公司总部科技项目(5200-201955096A-0-0-00)资助
  • 【文献出处】 电工技术学报 ,Transactions of China Electrotechnical Society , 编辑部邮箱 ,2023年02期
  • 【分类号】TM41;TM721.1
  • 【下载频次】33
节点文献中: 

本文链接的文献网络图示:

本文的引文网络