An uncertainty model has been proposed which is based on the black-box concept to evaluate the uncertainty of measurement and calibration in high voltage pulse divider.The initial model was proposed in principle,unnecessary variables in the formula could be omissible in the calibration experiment.For the model absent of uncertainty originating from calibration document,and resolving power of oscilloscope,the correction components which belong to the black-box model would be introduced to the formula to perf...