Numerical Research on the Influence of Heat Transfer Characteristics of Indirect Air Cooled Radiator Operating Around Half Cooling Tower Under Different Wind Directions
Indirect air cooled radiator performance is greatly influenced by the environmental factors. By using the numerical heat transfer(NHT) software called FLUENT,the flow and thermal characteristics of air cooling tower using indirect air cooled radiator(IACR) under natural draft for a 2 × 300 MW stage operation unit is simulated and analyzed. Under the environmental wind speed and directions of IACR assessment condition,the flow and heat transfer performance of IACR operation around half-tower is examined. The...