Traditional virtual synchronous generator control scheme can help inverters to realize primary frequency regulation and provide frequency support for microgrid. However, steady-state error exists by using this method. With improved control structure of virtual synchronous generator, function of secondary frequency regulation for island mode can be obtained to stabilize microgrid frequency. System stability is discussed through small signal equivalent analysis and root-locus method, and selection range of re...