110kV AIS+GIB母线优化布置电场强度评估

Evaluation of Electric Fields Strengthin AIS+GIB Configuration

  • 推荐 CAJ下载
  • PDF下载
  • 不支持迅雷等下载工具,请取消加速工具后下载。

【作者】 熊杰唐爱红潘小军杨惠源吴丹毛毳闽

【Author】 XIONG Jie;TANG Ai-hong;PAN Xiao-jun;YANG Hui-yuan;WU Dan;MAO Cui-min;School of Automation,Wuhan University of Technology;Hubei Electric Engneering Corporation;

【机构】 武汉理工大学自动化学院湖北省电力勘测设计院

【摘要】 以十堰220kV变电站工程110kV侧出线间隔为对象,分析了空气绝缘设备和SF6绝缘母线优化布置下的电场分布情况。根据电磁计算原理,借助有限元分析软件ANSYS建立了电场计算模型;通过有效的模型简化,在允许误差范围内减少了计算成本。结果表明,与变电站典型设计A-2方案相比,该优化布置方案在纵向尺寸缩减37.5%的情况下,电场强度峰值上升了8.6%,平均电场强度下降了14.7%,符合相关标准。

【Abstract】 Taking the optimal design for 110 kV outgoing line bays in 220 kV Shiyan substation engineering project as an example,the electric-field distribution in AIS and GIB optimal configuration was analyzed and a simulation model by ANSYS was established.The simplified models were built to reduce the difficulty of calculation.Compared with 220-A-2 universal design,this optimization scheme has an advantages of saving 37.5% horizontal dimension and 14.7% average electric-field strength.The maximal electric-field value only increase 8.6%,which will meet the professional standard.