The performance of the 10-stage LTD generator is investigated in experiments with some stages uncharged or untriggered.The result shows that both the current and the voltage decrease by almost 10%,20%and 30%,the pulse rise-time increases by 10,22 and 32ns and the pulse width increases by 13,23 and 48ns,for 1,2and 3malfunctioning stages respectively.Compared with the LTD generator in good condition,the equivalent circuit simulation of the LTD generator working abnormally demonstrates that the variation trend...