节点文献
两种40.5kV真空灭弧室电场和电势分布的对比研究
Electric Potential and Field Distributions of Two Types of 40.5 kV Vacuum Interrupters
【摘要】 建立了相同型号,不同结构的两种40.5 k V真空灭弧室的轴对称模型。计算并分析了两种真空灭弧室的主屏蔽罩对换前和对换后的电场分布和电势分布,对比了不同主屏蔽罩结构下的触头表面的有效面积,并分析了主屏蔽罩内表面的电场分布曲线。结果表明:型号相同的两个真空灭弧室内部电场分布及电势分布主要受到主屏蔽罩结构的影响,选择合适的主屏蔽罩结构可有效降低最大电场强度并改电场和电势分布。
【Abstract】 The electric potential and field distributions of Type-A and Type-B 40. 5 k V vacuum interrupters of the same model but with different axisymmetric structures,before and after exchanging their main-shields,were empirically approximated,mathematically modeled,numerically simulated in finite element method with software ANSYS. The influence of the exchange of the main-shields,on the field distributions on the main-shield surfaces and effective areas of the contact surfaces was investigated. The simulated results show that the geometry of the mainshield has a major impact on the distributions of the electric potential and field. The vacuum interrupter with TypeB main-shield outperforms that with Type-A main-shield. We suggest that design optimization of the main-shield structure may effectively reduce the maximum electric field and improve the potential and field distributions.
【Key words】 Vacuum interrupter; Ansys; Electric field calculation; Potential distribution; Main shield;
- 【文献出处】 真空科学与技术学报 ,Chinese Journal of Vacuum Science and Technology , 编辑部邮箱 ,2015年07期
- 【分类号】TM561.5
- 【被引频次】5
- 【下载频次】225