高压变频柜绝缘导线的局放原因分析及解决办法

Reason Analysis on Partial Discharge of Insulated Conductor for High Voltage Frequency Conversion Cabinet and Its Solutions

  • 推荐 CAJ下载
  • PDF下载
  • 不支持迅雷等下载工具,请取消加速工具后下载。

【作者】 朱泽慧张春辉张雨杨匀阳谢斯晗夏斌周达

【Author】 Zhu Zehui;Zhang Chunhui;Zhang Yu;Yang Yunyang;Xie Sihan;Xia Bin;Zhou Da;College of Electrical and Information Engineering, Changsha University of Science and Technology;Changsha Xinchang Power Technology Co., Ltd.;

【机构】 长沙理工大学电气与信息工程学院长沙信长电力科技有限公司

【摘要】 针对高压变频柜绝缘导线绑扎点附近出现白色附着物的现象进行分析和讨论。研究表明将绝缘导线之间微小的空气间隙类比于绝缘层内部有空气间隙,其空气间隙为局部放电创造条件,导致导线绝缘层之间发生局部放电时产生白色附着物。用MATLAB仿真对局部放电起始电压进行分析,提出了解决办法。

【Abstract】 An appearance of white attachments on the colligation position of insulated conductors in high voltage frequency conversion cabinet was analyzed and discussed. The tiny air gaps between the insulated conductors were in analogy to the air gaps in the insulation layer, and the air gaps would lead to partial discharge and produce white attachments between insulating layers of conductors. The partial discharge inception voltage was analyzed by MATLAB simulation, and corresponding solutions were put forward.

  • 【文献出处】 绝缘材料 ,Insulating Materials , 编辑部邮箱 ,2015年02期
  • 【分类号】TM832
  • 【下载频次】54
节点文献中: 

本文链接的文献网络图示:

本文的引文网络