2013年浙江省公共场所集中空调通风系统污染状况分析

Analysis on the contamination of central air conditioning ventilation systems in public places of Zhejiang province in 2013

  • 推荐 CAJ下载
  • PDF下载
  • 不支持迅雷等下载工具,请取消加速工具后下载。

【作者】 陈卫中王晓峰何升良任丽华蔡建民杨东波

【Author】 CHEN Wei-zhong;WANG Xiao-feng;HE Sheng-liang;REN Li-hua;CAI Jian-min;YANG Dong-bo;Zhejiang Provincial Centre for Disease Control and prevention;

【机构】 浙江省疾病预防控制中心

【摘要】 目的为了解浙江省集中空调通风系统卫生状况,以及公共场所集中空调卫生检测中存在的问题。方法对全省11个地市及义乌市的190家公共场所集中空调通风系统卫生指标进行检测。结果旅店、商场、医院、娱乐场所、写字楼5类公共场所检测指标均合格的占39.47%;10项指标的检测合格率为88.98%,其中送风中细菌总数和真菌总数合格率较低,分别为67.89%和78.95%,其余指标合格率均在80%以上,仅送风中β-溶血性链球菌合格率为100%。表明集中空调通风系统存在一定程度的污染。结论集中空调通风系统污染情况不容乐观,公共场所应做好空调系统的日常卫生管理和清洗消毒工作,保证空调系统运行期间室内空气品质。

【Abstract】 Objective To understand the sanitary conditions of central air conditioning ventilation system and find out the problems in the detection of public health central air- conditioning. Methods 190 air conditioning and ventilation systems in public places were test in 11 prefecture- level cities and Yiwu. Results 39. 47% of 5 categories,which include hotels,shopping malls,hospitals,places of entertainment,and office rooms,have qualified all detected indicators; the pass rate of 10 indicators is 88. 98%. Among these indicators,the total number bacteria and the total number of fungi in blowing- in air were 67. 89%and 78. 95%,which is quiet low. And the pass rates of remaining indicators are all above 80%,while only the pass rate of total number of β- hemolytic streptococcus in blow- in air is 100%. Therefore,a certain degree of pollution exists in the centralized air conditioning system. Conclusion Contamination in central air conditioning ventilation system is not optimistic. Daily health management,cleaning and disinfection of air- conditioning should be done well,ensuring indoor air quality in the operation of air- conditioning system.

  • 【文献出处】 中国卫生检验杂志 ,Chinese Journal of Health Laboratory Technology , 编辑部邮箱 ,2014年21期
  • 【分类号】R126.4
  • 【被引频次】2
  • 【下载频次】64
节点文献中: 

本文链接的文献网络图示:

本文的引文网络