节点文献

Influence of the Inverse-Time Protection Relays on the Voltage Dip Index

  • 推荐 CAJ下载
  • PDF下载
  • 不支持迅雷等下载工具,请取消加速工具后下载。

【作者】 高新科刘玡朋

【Author】 GAO Xin-ke;LIU Ya-peng;School of Electronic, Information and Electrical Engineering, Shanghai Jiaotong University;Institute of Information Technology, Luoyang Normal College;Qingdao Power Supply Company in Shandong Provincial Electric Power Company;

【机构】 School of Electronic, Information and Electrical Engineering, Shanghai Jiaotong UniversityInstitute of Information Technology, Luoyang Normal CollegeQingdao Power Supply Company in Shandong Provincial Electric Power Company

【摘要】 The probability-assessment analyses on the characteristic value of voltage dip by using Monte Carlo stochastic modeling method to stimulate the randomness of the short circuit fault are introduced. Using Matlab and Power Systems CAD(PSCAD), we design control interface which combines the electromagnetic transient simulation with the Monte Carlo method. Specifically, the designing of interface which is meant to employ the method of Matlab programming to control the electromagnetic transients including direct current(EMTDC)simulation is introduced. Furthermore, the influences of the protection devices on the voltage dip to ensure the authenticity and the referential reliability are simulated. A system with the inverse-time protection devices equipped on each line which can coordinate together is designed to cut off the short-circuit fault. The voltage dip of the designed system is assessed by the pre- and post-system average root mean square(RMS) variation frequency index, and the voltage dip index is compared with the Information Technology Industry Council(ITIC)curves. The simulation results demonstrate that the inverse-time relay protection equipments are well-coordinated,and the severity and the range of the voltage dip are influenced by the cooperation of the equipped inverse-time protection devices.

【Abstract】 The probability-assessment analyses on the characteristic value of voltage dip by using Monte Carlo stochastic modeling method to stimulate the randomness of the short circuit fault are introduced. Using Matlab and Power Systems CAD(PSCAD), we design control interface which combines the electromagnetic transient simulation with the Monte Carlo method. Specifically, the designing of interface which is meant to employ the method of Matlab programming to control the electromagnetic transients including direct current(EMTDC)simulation is introduced. Furthermore, the influences of the protection devices on the voltage dip to ensure the authenticity and the referential reliability are simulated. A system with the inverse-time protection devices equipped on each line which can coordinate together is designed to cut off the short-circuit fault. The voltage dip of the designed system is assessed by the pre- and post-system average root mean square(RMS) variation frequency index, and the voltage dip index is compared with the Information Technology Industry Council(ITIC)curves. The simulation results demonstrate that the inverse-time relay protection equipments are well-coordinated,and the severity and the range of the voltage dip are influenced by the cooperation of the equipped inverse-time protection devices.

【基金】 the Henan Tackle Key Problem of Science and Technology(No.102102210454);the Foundation of Education Committee of Henan Province(No.2011B520028)
  • 【文献出处】 Journal of Shanghai Jiaotong University(Science) ,上海交通大学学报(英文版) , 编辑部邮箱 ,2014年03期
  • 【分类号】TM714.2
  • 【被引频次】2
  • 【下载频次】58
节点文献中: 

本文链接的文献网络图示:

本文的引文网络