厦门市2009—2011年公共场所集中空调通风系统卫生状况分析

Analysis on Hygienic Status of Centralized Air Conditioning Ventilation System in Public Places of Xiamen in 2009—2011

  • 推荐 CAJ下载
  • PDF下载
  • 不支持迅雷等下载工具,请取消加速工具后下载。

【作者】 黄小金叶秀恋王宝珍陈剑锋洪华荣黄培枝骆和东

【Author】 Huang Xiaojin,Ye Xiulian,Wang Baozhen,Chen Jianfeng,Hong Huarong,Huang Peizhi,Luo Hedong

【机构】 福建省厦门市疾病预防控制中心福建医科大学教学基地

【摘要】 目的执行卫生部的管理办法,保证公共场所集中空调通风系统通风质量达到规范要求。方法依据《公共场所集中空调通风系统卫生规范》(卫监督发〔2006〕58号)的要求,于2009—2011年对厦门市相关单位集中空调通风系统可吸入颗粒物(PM10)、积尘、真菌总数、细菌总数和β–溶血性链球菌等进行检测。结果公共场所集中空调送风系统PM10、细菌总数、真菌总数合格率分别为93.6%、90.3%、96.8%,风管内表面积尘量、细菌总数、真菌合格率分别为99.3%、97.2%、95.6%,送风系统及风管内β–溶血性链球菌均未检出,2009年冷却塔水中的嗜肺军团菌检出率为29.2%。2010年和2011年冷却塔水中均未检测出嗜肺军团菌。结论目前厦门市公共场所集中空调通风系统卫生状况还存在一定的卫生隐患,在今后工作中要加强对集中空调微生物污染的预防控制。

【Abstract】 Objectives To ensure air quality in centralized air ventilation system in public places meeting the requirements of the national ministry of health management criterion.Methods According to Hygienic Standards for Centralized Air Conditioning Ventilation System in public places,PM10,dust,total count of fungi,the total count of aerobic bacterial,β-hemolytic streptococcus and legionella pneumophila were detected.Results The qualified rates of PM10,total count of fungi,the total count of aerobic bacterial were 93.6%,96.8% and,90.3% respectively;the qualified rates of the dust weight,the total count of aerobic bacterial and the total count of fungi in the inner surface of ventilation vessels were 99.3%,97.2% and 95.6%,respectively.There was no β-hemolytic streptococcus in wind supply system and ventilation vessels.The detection rate of legionella pneumophila in the water of cooling tower was 29.2% in 2009,and no legionella pneumophila was detected in 2010-2011.Conclusions Sanitary control should be strengthened to the central air conditioning ventilation system in some public places.

【基金】 福建省卫生厅宾馆酒店集中空调通风系统冷却塔军团菌检测项目
  • 【文献出处】 环境卫生学杂志 ,Journal of Environmental Hygiene , 编辑部邮箱 ,2013年01期
  • 【分类号】R126.4
  • 【被引频次】12
  • 【下载频次】117
节点文献中: 

本文链接的文献网络图示:

本文的引文网络