节点文献

超临界机组调试阶段水冷壁爆管原因分析及对策

Cause Analysis of Water-cooled Wall Tube Bursting During Trial Run in Supereritical Unit and Countermeasures

  • 推荐 CAJ下载
  • PDF下载
  • 不支持迅雷等下载工具,请取消加速工具后下载。

【作者】 柯浩孙涛阎光宗徐雪霞张晓昱郑相峰

【Author】 KE Hao,SUN Tao,YANG Guang-zong,XU Xue-xia,ZHANG Xiao-yu,ZHENG Xiang-feng( Hebei Electric Power Research Institute,Shijiazhuang 050021,China)

【机构】 河北省电力研究院

【摘要】 某超临界锅炉水冷壁在调试阶段发生爆管,从爆口处外观形貌、化学成分、金相组织、力学性能进行原因分析,可以判定此次爆管属于短时过热爆管,过热的原因推断为异物堵塞,并提出相应对策。

【Abstract】 Water-cooled wall tube bursting is hapened during trial run in 660 MW supereritical unit,it analyzed causations of bursting by macrostructure,chemical composition check,metallographic check,tensile testing.The results indicate that short time over temperature has led to the tube failure,because Water-cooled wall tube is blocked by foreign matters,and and the corresponding countermeasure is put forward.

【关键词】 水冷壁爆管短时过热堵塞
【Key words】 water-cooled wallburstingshort time over-heatingblock
  • 【分类号】TK227
  • 【下载频次】75
节点文献中: 

本文链接的文献网络图示:

本文的引文网络