无负压供水系统中水泵水锤的瞬态分析
Transient Simulation of Water Hammer in the No-negative-pressure Distribution System
【摘要】 针对某大型无负压泵站,应用一维流体软件FLOWMASTER对开泵、关泵和水泵变频过程进行暂停分析,结果表明:无负压设备在关泵、开泵、升频和降频过程中,均产生水锤现象,而且水锤迅速在整个供水管网内传递;无负压泵站前端管网的水锤压力变化较小,压力变化不超过0.01MPa,泵站下游管网的水锤压力变化较大,超过0.03MPa,水锤最大压力低于0.337MPa,低于管道的承压值。
【Abstract】 Pump units are the main part of the no-negative-pressure facility in the water distribution system.In order to achieve constant pressure of water supply and improve the life of pumps,starting pump,stopping pump and varying frequency are very common in the performance of the facility.In this article,the software of Flowmaster has been applied in network adjustment calculation based the data for the pumping stations with no-negative-pressure facility and pipe networks to predict the water hammer in starting pump,stopping pump and varying the frequency of pumps.The results represent that the model built by the author can predict the water hammer of the distribution system and water hammer is found to transfers along with the water pipe networks in starting pump,stopping pump and changing the frequency of pumps.After comparison of the results,smaller pressure change no less than 0.1 bar is found in the front part of network while pressure change over 0.03MPa emerges in the back part of network with the maximum of 0.337MPa,which never exceed the bearing level of pipes.
【Key words】 no-negative-pressure facility; water hammer; pump stopping; pump starting; variable frequency;