变压器油介损超标原因分析及处理
Analysis and treatment for over dielectric loss of transformer oil
【摘要】 对隔河岩电厂500 kV变压器的油介质损耗超标原因进行了分析,并采取了真空滤油机循环法、药粉滤纸法、XDK型高效吸附剂法等多种净油方式,对变压器绝缘油进行了净化处理,使油介质损耗超标问题得到解决。
【Abstract】 The factors caused over dielectric loss of the 500 kV transformer insulating oil of Geheyan Hydropower Plant are analyzed.The insulating oil is purified by means of vacuum circulating filtration,paper filtration,and XDK type high efficient absorbent.The oil quality comes back to the standard.
【关键词】 变压器;
油介损;
原因分析;
处理措施;
【Key words】 transformer; oil dielectric loss; cause analysis; treatment measures;
【Key words】 transformer; oil dielectric loss; cause analysis; treatment measures;