节点文献

首批国产750kV断路器绝缘拉杆故障分析

Fault Analysis of Insulation Pull Arm in the First Batch 750 kV Circuit-Breaker Made in China

  • 推荐 CAJ下载
  • PDF下载
  • 不支持迅雷等下载工具,请取消加速工具后下载。

【作者】 孙强尚勇唐开宇

【Author】 SUN Qiang,SHANG Yong,TANG Kai-yu(Northwest China Grid Company Limited,Xi’an 710049,Shaanxi Province,China)

【机构】 西北电网有限公司

【摘要】 介绍了我国首批国产750 kV断路器在现场发生的2起典型绝缘拉杆故障,对故障原因进行了分析,确定由于拉杆绝缘部分不同材料层间粘接工艺控制问题,造成内部电弧放电击穿,导致拉杆绝缘破坏。针对以上情况提出了改进工艺和增加对绝缘拉杆的局部放电和机械性能试验等措施。

【Abstract】 This paper introduced two typical accidents about insulation pull arms in the first batch 750 kV circuit breaks made in China,and analyzed the cause of faults.This paper confirms that the caster mater between different types of insulate materials is the main reason for internal arc discharge breakdown,which leads to insulation malfunction for pull arms.Based on the above situation,this paper proposes some suggestions,including improving process,adding the tests of partial discharge and mechanical performance for insulation pull arm.,etc.

【关键词】 750kV断路器绝缘拉杆绝缘故障
【Key words】 750 kVCircuit-breakInsulation pull armInsulation accident
  • 【文献出处】 电网与清洁能源 ,Power System and Clean Energy , 编辑部邮箱 ,2009年05期
  • 【分类号】TM561.3
  • 【被引频次】10
  • 【下载频次】230
节点文献中: 

本文链接的文献网络图示:

本文的引文网络