节点文献

电网谐波对消弧线圈接地系统的影响

The Impact of Power Grid Harmonics on Grounding System of Arc-suppression Coil

  • 推荐 CAJ下载
  • PDF下载
  • 不支持迅雷等下载工具,请取消加速工具后下载。

【作者】 金百荣李电

【Author】 JIN Bai-rong,LI Dian(Shaoxing Power Supply Company,Shaoxing 312000,China)

【机构】 绍兴电力局

【摘要】 为验证某制造厂新型自动调谐消弧线圈装置性能,笔者进行了消弧线圈成套装置金属接地、电阻接地、弧光接地等现场试验,结果发现,当电网具有较高谐波时,单相接地电流含有丰富的谐波成分,消弧线圈并不能补偿谐波接地电流,造成以谐波为主的残流值超标,影响补偿效果,对此问题应引起关注。

【Abstract】 In order to test the performance of new type automatic tuning arc-suppression coil of some factory,the metal grounding、 resistance grounding and arc grounding test of arc-suppression coil whole set tests were carried out.By analyzed the test result,abundant harmonic component was discovered in single-phase grounding current when power grid have more harmonics,and arc-suppression coil can not compensate for harmonic grounding currents.This will cause harmonic residual grounding current exceed the standard value,compensation effects be affected.It needs more attention to this question.

  • 【文献出处】 高压电器 ,High Voltage Apparatus , 编辑部邮箱 ,2009年04期
  • 【分类号】TM475
  • 【被引频次】16
  • 【下载频次】197
节点文献中: 

本文链接的文献网络图示:

本文的引文网络