节点文献

110kV线路接地距离Ⅲ段整定原则的探讨

Research of setting method of ground distance zone-Ⅲ protection for 110kV transmission line

  • 推荐 CAJ下载
  • PDF下载
  • 不支持迅雷等下载工具,请取消加速工具后下载。

【作者】 魏莉郑涛雷玉莲张育生

【Author】 WEI Li1, ZHENG Tao2, LEI Yu-lian1,ZHANG Yu-sheng1 ( 1. Guyuan Power Supply Bureau, Guyuan 756000, China; 2. North China Electric Power University, Beijing 102206, China )

【机构】 固原供电局华北电力大学

【摘要】 通过一起110kV线路接地距离Ⅲ段保护在线路末端变压器35kV侧母线故障时越级误动事件的分析,提出接地距离Ⅲ段保护定值及时限在整定上的改进措施。使110kV线路接地距离Ⅲ段保护定值和时限与相间距离Ⅲ段保护的定值及时限按照相同原则整定。既可以提高远后备灵敏度,同时加强了远后备对相邻电力设备安全性的保障。

【Abstract】 Based on analysis of mal-operation of ground distance zone-Ⅲ protection for 110kV transmission line which is caused by fault phase-to-phase occurred on 35kV busbar of transformer. An improved setting method for ground distance zone-Ⅲ protection is introduced in this paper. In order to improve the sensitivity and reliability of far back-up protection, setting values and operating time adopted in ground distance zone-Ⅲ protection should be equal to those in phase-to-phase distance zone-Ⅲ protection.

【基金】 国家自然科学基金资助项目(50607006)~~
  • 【文献出处】 电力系统保护与控制 ,Power System Protection and Control , 编辑部邮箱 ,2008年19期
  • 【分类号】TM773
  • 【被引频次】1
  • 【下载频次】130
节点文献中: 

本文链接的文献网络图示:

本文的引文网络