地铁站火灾烟气三维动态场模拟
A Three Dimensional Dynamic Field Simulation of Smoke in Subway Station Fire
【摘要】 由于城市地铁的建设在我国迅速发展,地铁站的火灾防范和安全疏散成为一个重要的研究课题。为了探讨地铁站火灾烟气的发展流动规律,笔者根据我国大多数现有地铁站的建筑结构模式建立了双层地铁车站的物理模型,并采用CFD的方法完成了火灾烟流三维动态的场模拟。在模拟中采用Rosseland辐射模型,将火源设定为放热量随时间变化的热源。计算结果表明在没有机械通风的情况下,烟气6分钟就将充满整个地铁站,人员难以在规范要求的时间内安全疏散。该研究成果可以为地铁站火灾发生时人员的安全疏散及烟气的控制提供一定的理论基础。
【Abstract】 Because of rapid development of subway in China, fire prevention and safe evacuation in subway station become an important research topic. In order to investigate the rule of smoke development and movement, a physical model of a two-layer subway station is established in the text based on most subway station in China. A three dimensional dynamic field simulation of smoke movement is accomplished through CFD, in which the Rosseland radiation model is adopted. The fire source is set as one the exothermic of which is changing with time. The results indicate that the subway station would fill of smoke in six minutes without mechanical ventilation and passengers could not be safely evacuated within the time limit. This study provides theoretical basis for smoke control and passenger evacuation during the fire of a subway station.
【Key words】 Subway station Fire Field-simulation Radiation Heat source Smoke;