虹桥国际机场国内候机楼空调冷冻水水泵节能改造

Energy Saving Reform of Chiller-pump of Air Conditioning Systemin Hongqiao International Airport Terminal Building

  • 推荐 CAJ下载
  • PDF下载
  • 不支持迅雷等下载工具,请取消加速工具后下载。

【作者】 于凌燕刘传聚徐健

【Author】 YU Ling-yan 1, LIU Chuan-ju 2, XU Jian 3(1.Shenyang Architecture University, Shenyang 100168, China; 2.Tongji University, Shanghai 200092, China;3.Shanghai Hongqiao International Airport Corporation, Shanghai 200335, China)

【机构】 沈阳建筑大学同济大学上海虹桥国际机场公司 辽宁沈阳100168上海200092上海200335

【摘要】 通过对虹桥机场侯机楼空调冷冻水系统的调研和测试,发现了冷冻水泵选型过大的问题,采用切削水泵叶轮的措施加以改进,并进行了叶轮切削量的计算。结果表明改造后节能效果明显,安全运行得到保障。

【Abstract】 On the basis of research and measuring to chiller water system of air-conditioning system in Hongqiao International Airport Terminal Building, we find the capacity of chiller pump is too large. We use the way of impeller-cutting to reform it and calculate the impeller-cutting quantity. The result indicates the energy consumption of chiller pump is saved and safe operation is guaranteed.

【关键词】 冷冻水泵流量扬程功率叶轮切削切削量
【Key words】 chiller-pumpflowliftpowerimpeller-cuttingimpeller-cutting quantity