节点文献
500kV同杆并架双回线路电气特性研究
Study on the Electrical Characteristic of 500 kV Common-Tower Double-Transmission Line
【摘要】 用EMTP程序模拟计算分析了500 kV湘潭—云田同杆并架双回线路(湘云线)的感应电流、电压及对系统不平衡度的影响等,为线路接地开关选择提出依据。验算线路对系统不平衡度影响的结果表明,线路两端500kV母线最大负序电压不平衡度为0.636%,流入湘潭发电机侧的最大负序电流不平衡度为0.70%,湘云同杆双回线不换位造成的负序电流和电压不平衡度都在允许范围内,不会给系统运行带来危害。
【Abstract】 Aiming at the 500 kV Xiangtan-Yuntian (Xiangyun Line) Common-tower double-transmission line’s inductive current, inductive voltage and the influences on the power system imbalance degree, the simulation, calculation and analysis is made for the line with EMTP program in order to bring forward the principles of choosing the grounding switch. And the influences of this line on the system imbalance degree are also checked to insure the safety of power system operation.
【关键词】 同杆并架双回路;
不平衡度;
感应电流及电压;
接地开关;
EMTP程序;
【Key words】 common-tower double-transmission line; imbalance degree; inductive current and voltage; grounding switch; EMTP program;
【Key words】 common-tower double-transmission line; imbalance degree; inductive current and voltage; grounding switch; EMTP program;
- 【文献出处】 高电压技术 ,High Voltage Engineering , 编辑部邮箱 ,2005年04期
- 【分类号】TM75
- 【被引频次】64
- 【下载频次】476