响洪甸抽水蓄能电站地下厂房渗水分析
Analysis of the leakage in the underground workshopof Xianghongdian Pumped Storage Station
【摘要】 响洪甸抽水蓄能电站在引水主洞充水后,地下厂房上游混凝土边墙多处出现渗漏水,厂房潮湿,严重影响机电设备运行的正常使用寿命和人身健康。通过现场渗漏水情况的详细勘测,对渗水原因进行了深入的分析和探讨,提出厂内集中引排和厂外封堵渗漏水通道的具体措施,并通过已采取的集中引排处理,厂内潮湿已明显改观,墙面已基本干燥。
【Abstract】 The underground workshop of Xianghongdian Pumped Storage Station became damp due to the leakage near the concrete sidewall on the upstream of the workshop after the main inlet was supplied with water,which did great harm to the proper usage of the machinery and power-generating equipment and the personal health. Based on the detailed investigation and surveying on the spot,the causes of the leakage are analyzed,and some countermeasures are suggested,such as concentrating drainage in the workshop and blocking the leakage passage on the outside of the workshop. By means of the treatment,the dampness has been improved obviously and the wall is dry on the whole.
- 【文献出处】 合肥工业大学学报(自然科学版) ,Journal of Hefei University of Technology(Natural Science) , 编辑部邮箱 ,2004年04期
- 【分类号】TV223.4
- 【下载频次】71