变频介损仪在CVT不拆线试验中的应用

The Use of the Frequency-Conversion Bridge in Test of the Capacitor Voltage Transformer without Disconnecting the Wire

  • 推荐 CAJ下载
  • PDF下载
  • 不支持迅雷等下载工具,请取消加速工具后下载。

【作者】 黄涛刘艳李国伟

【Author】 Huang Tao, Liu Yan, Li Guowei (Foshan Power Supply Branch GPG, Goshan 528000, China)

【机构】 广东省广电集团有限公司佛山供电分公司广东省广电集团有限公司佛山供电分公司 佛山528000佛山528000佛山528000

【摘要】 为较简便地解决不拆线试验CVT中的干扰和误差 ,介绍了用变频介损试验的方法及注意事项 ,测量低压电容时 ,中间变压器中压连结电压宜 <2 5kV ,工作频率宜为 4 0~ 4 7.5Hz。现场试验表明 ,该法可消除现场干扰所得数据与拆线法极为接近 ,完全满足试验要求。

【Abstract】 To resolve the error and disturbance with a simple way for the test of CVT without disconnecting the wires, this paper introduces how to perform the test on CVT without disconnecting the wire with the frequency-conversion bridge, and what we should pay attention to in the test. When C2 is measured, the voltage of the inter transformer should be less than 2.5 kV, and the test frequency is between 40 to 47.5 Hz. Test data make it clear that this method adapts to on-site test.

  • 【文献出处】 高电压技术 ,High Voltage Engineering , 编辑部邮箱 ,2004年07期