节点文献
弧线管传热与污垢性能的实验研究
EXPERIMENTAL INVESTIGATION ON THE FOULING CHARACTERISTICS AND THE HEAT TRANSFER PERFORMANCES OF ARC LINE TUBE
【摘要】 本研究先进行了弧线管的传热性能实验,得出了弧线管管内强制对流换热关联式。以硬度 800 mg/L的人工硬水作为工质,在流速 0.20 m/s,管外水浴温度 80℃和相同管内工质入口温度的条件下,进行了弧线管及其对应光管管内污垢的对比实验。结果表明,弧线管有良好的传热与阻垢两方面的综合性能。
【Abstract】 This paper describes the results of heat transfer performance tests for cooling waterflowing inside the arc line tube. Based on the experimental data, a dimensionless correlation for forcedconvection heat transfer inside the arc line tube is got. Moreover the comparative fouling experimentswere carried out between the arc line tube and its corresponding plain tube. The experimental workingfluid was 800 mg/L hardness water inside tubes, and the experiments were done under the conditionof 0.20 m/s liquid velocity, temperature of 80℃ at the water tank, and the same inlet temperature ofworking fluid inside the tubes. The experimental results show that the arc line tube has an advantageboth in heat transfer performance in and anti-fouling performance over the plain tube.
- 【文献出处】 工程热物理学报 ,Journal of Engineering Thermophysics , 编辑部邮箱 ,2004年03期
- 【分类号】TK124
- 【被引频次】26
- 【下载频次】191