基于小波启动的故障分量相角比差发电机定子接地保护
A NEW PHASE-ANGLE DIFFERENTIAL PROTECTION FOR GENERATOR STATOR GROUND FAULT WITH WAVELET TRANSFORM START-UP COMPONENT
【摘要】 分析了发电机发生定子接地故障后,机端和中性点侧三次谐波电压相角变换的特性。在此基础上,提出基于小波启动的故障分量相角差动定子接地保护新方案,并研制出相应的保护模块。理论分析及实验研究均表明,该方案适用于各种接地方式的发电机,具有更高的灵敏度和可靠性。
【Abstract】 This paper analyzes the characteristic of the third-harmonic voltages at the generator neutral and the terminals under different operation conditions. According to that, a new 100% coverage protection scheme based on phase-angle differential of the fault contributed third-harmonic voltage at the terminals and the neutral is presented, and the fault initialized by a wavelet transform start-up component. The corresponding protection equipment is also introduced. Both simulation and experimental results show that the new approach can obtain the high sensitivity and reliability the great generator required.
【Key words】 stator ground protection; third-harmonic zero-sequence voltage; wavelet transform; fault component;
- 【文献出处】 电力系统自动化 ,Automation of Electric Power Systems , 编辑部邮箱 ,2004年13期
- 【分类号】TM307
- 【被引频次】7