节点文献
国家大剧院观众厅空调系统和气流组织方式的设计和分析
Design analysis of air conditioning and air distribution in the auditoria of the national theatre
【摘要】 介绍了观众厅座椅下送风方案。通过对置换通风和空调系统下送风方式的分析和实测 ,总结出这种气流组织的设计计算方法。全年能耗分析显示 ,为达到高标准的卫生和舒适要求采用 30m3/h人均新风量的椅下送风空调方式 ,比 1 5m3/h人均新风量的混风变新风比空调系统制冷量增加 5 0 .9%。
【Abstract】 Describes the under-seat air supply mode adopted in the project. Provides a procedure of design and calculation based on analyses and field measurement. An annual energy analysis shows that 50.9% more in the cooling capacity is required for the adopted under-seat air supply mode to meet higher standard of comfort and indoor air quality with 30 cubic metre per hour per person than that by using a mixing air conditioning system with a common fresh air supply of 15 cubic metre per hour per person.
【关键词】 国家大剧院;
观众厅;
椅下送风;
置换通风;
设计计算;
能耗分析;
【Key words】 national theatre; auditorium; under-seat air supply; displacement ventilation; design calculation; energy analysis;
【Key words】 national theatre; auditorium; under-seat air supply; displacement ventilation; design calculation; energy analysis;
- 【文献出处】 暖通空调 ,Hv & Ac , 编辑部邮箱 ,2003年03期
- 【分类号】TU831.8
- 【被引频次】68
- 【下载频次】1053