节点文献
10kV小电阻接地系统接地变压器零序保护误动机理研究
Study on the misoperation mechanism of zero sequence protection of grounding transformer on low resistance grounded 10 kV system
【摘要】 以某变电站 1 0kV小电阻接地系统为背景 ,针对屡次出现的接地变压器零序保护误动现象 ,建立了1 0kV配电网的数学模型 ,并进行了理论分析和Matlab数值仿真 ,提出了线路参数不对称及线路非金属性接地两个因素共同作用 ,导致 1 0kV小电阻接地系统运行方式下接地变压器零序保护误动的客观原因 ,以及系统的设计、安装、管理等人为原因。同时给出了检查 1 0kV出线电缆绝缘情况及建立零序电流监测装置等的相应的防范措施 ,以防止此类故障的发生
【Abstract】 This paper is for low resistance grounded 10kV substation.The misoperation of zero sequence protection in grounding transformer that happened repeatedly was analysed theoretically.Objective causes and artificial causes were addressed.Corresponding suggestions were also presented in this paper to avoid this kind of misoperation.
【关键词】 小电阻接地系统;
零序保护;
故障机理;
10kV配电网;
【Key words】 low resistance grounded system; zero sequence protection; misoperation mechanism; 10kV distribution network;
【Key words】 low resistance grounded system; zero sequence protection; misoperation mechanism; 10kV distribution network;
- 【文献出处】 继电器 ,Relay , 编辑部邮箱 ,2003年01期
- 【分类号】TM862
- 【被引频次】22
- 【下载频次】415