500kV隔离开关操作中燃弧引起的感应过电压

Induced overvoltage caused by arcing during operation of 500 kV disconnecting switches

  • 推荐 CAJ下载
  • PDF下载
  • 不支持迅雷等下载工具,请取消加速工具后下载。

【作者】 李长益魏旭张劲松

【Author】 LI Chang yi, WEI Xu, ZHANG Jin song (Jiangsu Electric Power Scientific & Research Institute, Nanjing 210036, China)

【机构】 江苏省电力科学研究院江苏省电力科学研究院 江苏南京210036江苏南京210036江苏南京210036

【摘要】 介绍了针对上河变电站几次 5 0 0 k V隔离开关操作引起的 40 0 V操作电源端子箱内熔丝熔断事件进行的现场试验。试验结果表明 ,隔离开关操作时 ,由于 5 0 0 k V串内连接线和 40 0 V电源线间存在电磁耦合 ,在40 0 V操作电源供电母线上有较高的感应电压存在。为降低感应电压 ,提出了铺设屏蔽电缆或暂时在电源母线上并联电容器的解决方案

【Abstract】 Test was made at site to investigate several accidents of fuse broken in 400 V operating power supply terminal box occurred during operation of 500 kV disconnector. The high inductive voltage existed in 400 V power supply bus line indicated by the test result during the operation of the disconnector is due to the electromagnetic coupling existing between 500 kV high voltage line and 400 V power supply line. To reduce the inductive voltage, shielded cable should be laid, or capacitor should be paralleled to power supply line temporarily.

  • 【文献出处】 华东电力 ,East China Electric Power , 编辑部邮箱 ,2003年04期
  • 【分类号】TM564
  • 【被引频次】5
  • 【下载频次】168
节点文献中: 

本文链接的文献网络图示:

本文的引文网络