节点文献
10kV小电阻接地系统特殊问题的研究
Study on Special Problems of 10 kV Systems with Low Resistance Grounding
【摘要】 提出了 1 0 k V小电阻接地系统的系统模型和节点电压方程 ,分析了该系统电缆线路对地电容参数不对称所引起的流过接地变压器中性点的零序电流的变化规律、高压侧出现单相接地故障对低压侧的影响及变电所接地网接地不良所产生的接地变压器中性点零序电压升高 ,并通过仿真算例证实了参数不对称和接地不良可能导致接地变压器零序电流保护误动
【Abstract】 This paper uses node method to illustate that asymmetric line capacitance parameter will generate zero sequence current which flows the neutral point of earthing transformer in 10 kV low resistance grounded system, and shows that if grounding network of substation is imperfect, the zero sequence voltage will increase, finally, gives the conclusion through simulation that zero sequence current protection may misoperate.
- 【文献出处】 高电压技术 ,High Voltage Engineering , 编辑部邮箱 ,2003年05期
- 【分类号】TM862
- 【被引频次】22
- 【下载频次】334