节点文献
基于重采样的三相谐波检测瞬时无功功率法
INSTANTANEOUS HARMONICS DETE CTING METHOD FOR THREE-PHASE CIRCUITS BASED ON RESAMPLING
【摘要】 提出了基于重采样的谐波检测方法 ,克服了数字化谐波检测瞬时无功功率法计算量大的缺点。当信号的最高频率为 ω时 ,第 1次采样频率为 ωf≥ 4ω。需要补偿 N′次以下的谐波电流时 ,重采样频率应不小于 (N′+1 +n) ω0 (ω0 为基波频率 )。当一个周期内的采样点数为 N1时 ,重采样频率为ωmin=(N1/4)ω0 。在重采样的基础上 ,继承了瞬时无功功率理论谐波检测方法的思想——将基波电流转变成直流分量 ,据此设计了一个数字谐波检测系统。仿真实验表明 ,该系统既具有数字系统的准确性和稳定性 ,又克服了数字滤波器计算量大和实时性差的问题 ,其动态跟随性有所改善
【Abstract】 A method for harmonic detecting based on resampling theory is proposed. It can improve the dynamic characteristics of digital filters. If the highest frequency in signal spectrum is ω, the first sampling frequency will be ω f≥4ω. When the active power filter (APF) is designed to compensate N′th harmonic currents, the resampling frequency should not be less than (N′+1+n)ω 0, (where ω 0 is the fundamental frequency). If the sampled data is N 1 in a period, the resampling frequency is ω min= (N 1/4)ω 0. Furthermore, a digital harmonic detecting system based on resampling, inheriting the core idea of the instantaneous detecting method, is designed. That is, transform the fundamental currents into DC component. Simulation shows that this system not only has accuracy and stability, but also overcomes the long existent weakness of large amount of calculation for the design of digital filter and poor on-line response characteristics and bad dynamic following performance of digital filters.
【Key words】 harmonic measurement; active power filter; resampling; spectrum aliasing;
- 【文献出处】 电力系统自动化 ,Automation of Electric Power Systems , 编辑部邮箱 ,2003年12期
- 【分类号】TN713
- 【被引频次】48
- 【下载频次】276